Zusammenfassung: 
The topic of this thesis is an operational test in the plant Lägerdorf measuring CO, O2 and temperature along the calciner aiming at optimized set points for calciner temperature. Kiln stops and CO stratifications could be reduced.
Data for this study were collected in several measuring campaigns in August and September 2016. Lowering the temperature of the calciner from 930 °C to 890 °C in ste...